Every apparatus manufactured
with a fixed generator
is load tested by a UL representative prior to final
delivery.
UL CERTIFIED TEST
The generator and all related electrical systems are
independently tested and certified in writing by Underwriters
Laboratories (UL). The testing conforms to NFPA 1901,
Chapter 23.16.2 requirements. The wiring and permanently
connected devices and equipment are subjected to a
dielectric voltage withstand test of 900 volts for
1 minute.
The dielectric tester (shown in photo) has a 500 volt-amperes
(VA) or larger transformer, with a sinusoidal output
voltage that can be verified.
The test is conducted as follows:
1. Isolate the power source from the panel board and
disconnect any solid state low voltage components.
2. Connect one lead of the dielectric tester to all
the hot and neutral busses tied together.
3. Connect the other lead to the fire apparatus frame
or body.
4. Close any switches and circuit breakers in the
circuits.
5. Apply the dielectric voltage for 1 minute in accordance
with the testing equipment manufacturer's instructions.
Electrical light towers, floodlights, motors, fixed
appliances, and portable generators (as applicable)
are operated at their full rating or capacity for
two hours to ensure proper operation.
Testing procedures are conducted as outlined in NFPA
1901, Chapter 23.16.5.3. The results of each test
are recorded on an appropriate form and provided with
the delivery documentation.
Tractor/Trailer UL testing in
process 40kw PTO application. Full load
is applied from the generator directly to the load
bank.
Note umbilical connection from tractor to trailer
is plugged
directly into the Load Bank. Meters are monitored
by UL
representative throughout the duration of the test.